{"id":385181,"date":"2024-10-20T03:29:29","date_gmt":"2024-10-20T03:29:29","guid":{"rendered":"https:\/\/pdfstandards.shop\/product\/uncategorized\/bs-en-iec-61243-12021\/"},"modified":"2024-10-26T06:19:44","modified_gmt":"2024-10-26T06:19:44","slug":"bs-en-iec-61243-12021","status":"publish","type":"product","link":"https:\/\/pdfstandards.shop\/product\/publishers\/bsi\/bs-en-iec-61243-12021\/","title":{"rendered":"BS EN IEC 61243-1:2021"},"content":{"rendered":"

IEC 61243-1:2021 is applicable to portable voltage detectors, with or without built-in power sources, to be used on electrical systems for voltages of 1 kV to 800 kV AC, and frequencies of 50 Hz and\/or 60 Hz. This document applies only to voltage detectors of capacitive type used in contact with the bare part to be tested, as a complete device including its insulating element or as a separate device, adaptable to an insulating stick which, as a separate tool, is not covered by this document (see 4.4.2.1 for general design). Other types of voltage detectors are not covered by this document. Self ranging voltage detectors (formally “multi range voltage detectors”) are not covered by this document. Some restrictions or formal interdictions on their use are applicable in case of switchgear of IEC 62271 series design, due to insulation coordination, on overhead line systems of electrified railways (see Annex B) and systems without neutral reference. For systems without neutral reference, the insulating level is adapted to the maximum possible voltage to the earth (ground). Products designed and manufactured according to this document contribute to the safety of users provided they are used by persons trained for the work, in accordance with the hot stick working method and the instructions for use. Except where otherwise specified, all the voltages defined in this document refer to values of phase-to-phase voltages of three-phase systems. In other systems, the applicable phase-to-phase or phase-to-earth (ground) voltages are used to determine the operating voltage. This third edition cancels and replaces the second edition published in 2003 and Amend-ment 1:2009. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) The scope is more precise, stating that only bare contact to the part to be tested is reliable for these contact voltage detectors. The rationale is that tests on painted or coated conductors have led to wrong indications, as this non-conductive paint or coat acts as a capacitor with different capacity according to the thickness. This capacity has an effect on the threshold voltage. b) A contact probe is introduced as a new type of non-conductive contact electrode. c) A new type “exclusively outdoor type” has been defined and implemented into the requirements and test procedure.d) A selector for voltage and frequency is allowed if foreseeable misuse is excluded. e) The marking for voltage detectors with low interference voltage has been made more precise. f) The indication groups have been made more precise and requirements and tests for the “ready to operate state” and “stand-by state” added. g) Requirements and tests for electromagnetic compatability have been implemented. h) An example for good electrical connection for the tests is introduced.<\/p>\n

PDF Catalog<\/h4>\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n
PDF Pages<\/th>\nPDF Title<\/th>\n<\/tr>\n
2<\/td>\nundefined <\/td>\n<\/tr>\n
5<\/td>\nAnnex ZA(normative)Normative references to international publicationswith their corresponding European publications <\/td>\n<\/tr>\n
7<\/td>\nEnglish
CONTENTS <\/td>\n<\/tr>\n
11<\/td>\nFOREWORD <\/td>\n<\/tr>\n
13<\/td>\nINTRODUCTION <\/td>\n<\/tr>\n
14<\/td>\n1 Scope
2 Normative references <\/td>\n<\/tr>\n
15<\/td>\n3 Terms and definitions <\/td>\n<\/tr>\n
19<\/td>\n4 Requirements
4.1 General requirements <\/td>\n<\/tr>\n
20<\/td>\n4.2 Functional requirements
4.2.1 Clear indication <\/td>\n<\/tr>\n
21<\/td>\n4.2.2 Clear perceptibility <\/td>\n<\/tr>\n
22<\/td>\n4.2.3 Temperature and humidity dependence of the indication
Tables
Table 1 \u2013 Indication group <\/td>\n<\/tr>\n
23<\/td>\n4.2.4 Frequency dependence
4.2.5 Response time
4.2.6 Power source dependability
4.2.7 Testing element
4.2.8 Non-response to DC voltage
4.2.9 Time rating
4.2.10 Electromagnetic compatibility (EMC)
4.3 Electrical requirements
4.3.1 Insulating material
Table 2 \u2013 Climatic categories <\/td>\n<\/tr>\n
24<\/td>\n4.3.2 Protection against bridging
4.3.3 Resistance against sparking
4.4 Mechanical requirements
4.4.1 General
4.4.2 Design
4.4.3 Dimensions, construction <\/td>\n<\/tr>\n
25<\/td>\nFigures
Figure 1 \u2013 Examples of designs of voltage detectors of capacitive type <\/td>\n<\/tr>\n
26<\/td>\nTable 3 \u2013 Minimum length of the insulating element (Li) of a voltage detector as a complete device <\/td>\n<\/tr>\n
27<\/td>\n4.4.4 Grip force and deflection
4.4.5 Vibration resistance
4.4.6 Drop resistance
4.4.7 Shock resistance
4.5 Markings <\/td>\n<\/tr>\n
28<\/td>\n4.6 Documents for the user
4.7 Instructions for use
4.8 Requirements in case of reasonably foreseeable misuse of the selector
4.8.1 Initial position of the selector
4.8.2 Voltage indication at an incorrect low position of the selector (where relevant)
5 Specific requirements
5.1 For insulating element of a voltage detector as a complete device
5.1.1 Dielectric strength
5.1.2 Leakage current
5.2 Insulation of the indicator casing of voltage detector as a separate device
5.3 Stand-by state
5.4 Ready to operate state <\/td>\n<\/tr>\n
29<\/td>\n6 Tests
6.1 General
6.1.1 Testing provisions
6.1.2 Atmospheric conditions
6.1.3 Tests under wet conditions
6.1.4 Type test <\/td>\n<\/tr>\n
30<\/td>\n6.1.5 Test methods <\/td>\n<\/tr>\n
31<\/td>\n6.2 Function tests
6.2.1 Clear indication <\/td>\n<\/tr>\n
32<\/td>\nFigure 2 \u2013 Examples of suitable means for ensuring appropriate contact between a contact electrode and the ball electrode <\/td>\n<\/tr>\n
34<\/td>\nFigure 3 \u2013 Ball and ring test set-up (see 6.2.1 and 6.2.5) <\/td>\n<\/tr>\n
36<\/td>\nFigure 4 \u2013 Test set-up with bars (see 6.2.1) <\/td>\n<\/tr>\n
38<\/td>\nFigure 5 \u2013 Circuit connections for clear indication tests (see 6.2.1) <\/td>\n<\/tr>\n
39<\/td>\nTable 4 \u2013 Selection of the test set-up for the influence of in-phase interference field
Table 5 \u2013 Distance G (see Figure 5d) <\/td>\n<\/tr>\n
40<\/td>\nTable 6 \u2013 Selection of the test set-up for the influence of phase opposition interference field
Table 7 \u2013 Selection of the test set-up for the influence of interference voltage <\/td>\n<\/tr>\n
42<\/td>\n6.2.2 Electromagnetic compatibility (EMC)
Table 8 \u2013 EMC parameters
Table 9 \u2013 Performance criteria for all the EMC tests
Table 10 \u2013 Test parameters for emission limit <\/td>\n<\/tr>\n
43<\/td>\n6.2.3 Clear perceptibility of visual indication <\/td>\n<\/tr>\n
44<\/td>\nFigure 6 \u2013 Test set-up for measurement of clear perceptibility of visual indication (see 6.2.3.1) <\/td>\n<\/tr>\n
45<\/td>\n6.2.4 Clear perceptibility of audible indication <\/td>\n<\/tr>\n
46<\/td>\nFigure 7 \u2013 Test set-up for measurement of clear perceptibility of audible indication (see 6.2.4.1) <\/td>\n<\/tr>\n
47<\/td>\n6.2.5 Frequency dependence
6.2.6 Response time
6.2.7 Power source dependability <\/td>\n<\/tr>\n
48<\/td>\n6.2.8 Check of testing element
6.2.9 Non-response to DC voltage
6.2.10 Time rating <\/td>\n<\/tr>\n
49<\/td>\n6.3 Dielectric tests
6.3.1 Insulating material for tubes and rods for voltage detectors as a complete device <\/td>\n<\/tr>\n
50<\/td>\n6.3.2 Protection against bridging for indoor and outdoor type voltage detectors
Table 11 \u2013 Selection of the test set-up and type of test <\/td>\n<\/tr>\n
53<\/td>\nFigure 8 \u2013 Test set-up for protection against bridging and spark resistance (see 6.3.2 and 6.3.4)
Table 12 \u2013 Distance d1 for the bridging test set-up <\/td>\n<\/tr>\n
55<\/td>\n6.3.3 Protection against bridging for outdoor type voltage detector
Table 13 \u2013 Dimensions for the concentric rings and band electrodes <\/td>\n<\/tr>\n
56<\/td>\nFigure 9 \u2013 Test for protection against bridging for outdoor type voltage detector <\/td>\n<\/tr>\n
57<\/td>\n6.3.4 Spark resistance
6.4 Mechanical tests
6.4.1 Visual and dimensional inspection
6.4.2 Grip force and deflection (only applicable for voltage detector as a complete device)
Table 14 \u2013 Selection of the test set-up for the spark resistance test <\/td>\n<\/tr>\n
58<\/td>\n6.4.3 Vibration resistance
Figure 10 \u2013 Test set-up for grip force <\/td>\n<\/tr>\n
59<\/td>\n6.4.4 Drop resistance
6.4.5 Shock resistance
6.4.6 Climatic dependence
Figure 11 \u2013 Drop resistance test \u2013 Diagonal position <\/td>\n<\/tr>\n
60<\/td>\nFigure 12 \u2013 Curve of test cycle for climatic dependence <\/td>\n<\/tr>\n
61<\/td>\n6.4.7 Durability of markings
7 Specific tests
7.1 Leakage current for voltage detector as a complete device
7.1.1 General
7.1.2 Leakage current under dry conditions <\/td>\n<\/tr>\n
62<\/td>\n7.1.3 Leakage current under wet conditions (outdoor type and exclusively outdoor type)
Figure 13 \u2013 Arrangement for leakage current tests under dry conditions for voltage detector as a complete device <\/td>\n<\/tr>\n
63<\/td>\n7.1.4 Alternative test for voltage detectors having completed the production phase
7.2 Test for stand-by state
7.3 Test for ready to operate state
Figure 14 \u2013 Arrangement for leakage current tests under wet conditions for outdoor type voltage detector as a complete device <\/td>\n<\/tr>\n
64<\/td>\n8 Test for reasonably foreseeable misuse of the selector
8.1 Initial position of the selector
8.2 Voltage indication at incorrect low position of the selector (where relevant)
9 Conformity assessment of voltage detectors having completed the production phase
10 Modifications <\/td>\n<\/tr>\n
65<\/td>\nAnnexes
Annex A (normative) Suitable for live working; double triangle (IEC\u201160417\u20115216:2002\u201110) <\/td>\n<\/tr>\n
66<\/td>\nAnnex B (normative) Instructions for use <\/td>\n<\/tr>\n
68<\/td>\nAnnex C (normative) Chronology of type tests
Table C.1 \u2013 Sequential order for performing type tests <\/td>\n<\/tr>\n
69<\/td>\nTable C.2 \u2013 Type tests out of sequence <\/td>\n<\/tr>\n
70<\/td>\nAnnex D (informative) Classification of defects and tests to be allocated
Table D.1 \u2013 Classification of defects and associated requirements and tests <\/td>\n<\/tr>\n
72<\/td>\nAnnex E (informative) Rationale for the classification of defects
Table E.1 \u2013 Rationale for the classification of defects <\/td>\n<\/tr>\n
75<\/td>\nAnnex F (informative) Information and guidelines on the use of the limit mark and of a contact electrode extension
F.1 General
F.2 Situation when using a voltage detector as a complete device
Figure F.1 \u2013 Insulation element of a voltage detector as a complete device <\/td>\n<\/tr>\n
76<\/td>\nFigure F.2 \u2013 Example of positioning of a voltage detector in contact with a live part without obstacles from other live parts <\/td>\n<\/tr>\n
77<\/td>\nF.3 Situation when using a voltage detector as a separate device
Figure F.3 \u2013 Example of incorrect positioning of a voltage detector with the limit mark between two live parts
Figure F.4 \u2013 Usual way of managing the use of the voltage detector for maintaining the insulation distance between the limit mark and the hand guard <\/td>\n<\/tr>\n
78<\/td>\nFigure F.5 \u2013 Usual ways of managing the use of the voltage detector as a separate device for assuring the appropriate insulation for the user <\/td>\n<\/tr>\n
79<\/td>\nAnnex G (informative) In-service care
G.1 General
G.2 Testing <\/td>\n<\/tr>\n
80<\/td>\nTable G.1 \u2013 In-service testing <\/td>\n<\/tr>\n
81<\/td>\nAnnex H (informative) Information for the next maintenance
H.1 Overhead line test
H.1.1 Rationale
H.1.2 Proposal for an improved test (will be discussed within the next maintenance)
H.2 Threshold deviation ratio category (deviation category) for voltage detectors of category L
H.2.1 Rationale
H.2.2 Proposal for a new requirement (will be discussed within the next maintenance)
H.3 Phase opposition test for voltage detectors of category L
H.3.1 Rationale
H.3.2 Proposal for an improved test (will be discussed within the next maintenance) <\/td>\n<\/tr>\n
82<\/td>\nH.4 Non-contact behaviour of voltage detectors of category L
H.4.1 Rationale
H.4.2 Proposal for a new test (will be discussed within the next maintenance)
Table H.1 \u2013 Maximum distances for early detection <\/td>\n<\/tr>\n
83<\/td>\nBibliography <\/td>\n<\/tr>\n<\/table>\n","protected":false},"excerpt":{"rendered":"

Live working. Voltage detectors – Capacitive type to be used for voltages exceeding 1 kV AC<\/b><\/p>\n\n\n\n\n
Published By<\/td>\nPublication Date<\/td>\nNumber of Pages<\/td>\n<\/tr>\n
BSI<\/b><\/a><\/td>\n2021<\/td>\n84<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n","protected":false},"featured_media":385188,"template":"","meta":{"rank_math_lock_modified_date":false,"ep_exclude_from_search":false},"product_cat":[552,2641],"product_tag":[],"class_list":{"0":"post-385181","1":"product","2":"type-product","3":"status-publish","4":"has-post-thumbnail","6":"product_cat-29-260-99","7":"product_cat-bsi","9":"first","10":"instock","11":"sold-individually","12":"shipping-taxable","13":"purchasable","14":"product-type-simple"},"_links":{"self":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product\/385181","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/types\/product"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/media\/385188"}],"wp:attachment":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/media?parent=385181"}],"wp:term":[{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product_cat?post=385181"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product_tag?post=385181"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}